我们有一台 APC Smart UPS 1500。“更换电池”指示灯亮起,apcupsd 报告:

Emergency! Batteries have failed on UPS xxxx. Change them NOW
Run Code Online (Sandbox Code Playgroud)

不过从这篇文章来看,

http://sturgeon.apcc.com/kbasewb2.nsf/for+external/f39c4312fcaf7b948525679a005ebb78?OpenDocument

好像不是很清楚需要更换UPS电池。奇怪的是,根据有关 UPS 的信息,在 42.9% 负载下以 27.7V 运行 11 分钟的运行时间还不错。

关于下一步要尝试什么的任何想法?我们是非营利组织,金钱一个对象。用一年左右的时间更换电池将是一种耻辱。

# apcaccess status
APC      : 001,041,1017
DATE     : Thu Mar 29 13:01:41 EDT 2012
HOSTNAME : oreilly2
VERSION  : 3.14.6 (16 May 2009) debian
UPSNAME  : xxxx
CABLE    : Custom Cable Smart
MODEL    : Smart-UPS 1500
UPSMODE  : Stand Alone
STARTTIME: Thu Mar 29 12:57:30 EDT 2012
STATUS   : ONLINE
LINEV    : 112.3 Volts
LOADPCT  :  42.9 Percent Load Capacity
BCHARGE  : 100.0 Percent
TIMELEFT :  11.0 Minutes
MBATTCHG : 5 Percent
MINTIMEL : 3 Minutes
MAXTIME  : 0 Seconds
OUTPUTV  : 112.3 Volts
SENSE    : High
DWAKE    : -01 Seconds
DSHUTD   : 090 Seconds
LOTRANS  : 106.0 Volts
HITRANS  : 127.0 Volts
RETPCT   : 000.0 Percent
ITEMP    : 23.8 C Internal
ALARMDEL : Always
BATTV    : 27.7 Volts
LINEFREQ : 60.0 Hz
LASTXFER : No transfers since turnon
NUMXFERS : 0
TONBATT  : 0 seconds
CUMONBATT: 0 seconds
XOFFBATT : N/A
SELFTEST : NO
STATFLAG : 0x07000008 Status Flag
SERIALNO : AS0603298896
BATTDATE : 2006-01-14
NOMOUTV  : 120 Volts
NOMBATTV :  24.0 Volts
FIRMWARE : 601.3.D USB FW:1.5
APCMODEL : Smart-UPS 1500
END APC  : Thu Mar 29 13:02:12 EDT 2012
Run Code Online (Sandbox Code Playgroud)

运行 upstest 时出错

You are using a SMART cable type, so I'm entering SMART test mode
mode.type = USB_UPS
Setting up the port ...
Hello, this is the apcupsd Cable Test program.
This part of apctest is for testing Smart UPSes.
Please select the function you want to perform.

1) Query the UPS for all known values
2) Perform a Battery Runtime Calibration
3) Abort Battery Calibration
4) Monitor Battery Calibration progress
5) Program EEPROM
6) Enter TTY mode communicating with UPS
7) Quit

Select function number: 2

First ensure that we have a good link and
that the UPS is functionning normally.
Simulating UPSlinkCheck ...
YWrote: Y Got:
getline failed. Apparently the link is not up.
Giving up.
Run Code Online (Sandbox Code Playgroud)

hma*_*ett 6

执行断流测试。这将告诉您电池的实际运行时间,而不是理论运行时间。它将负载切换到电池,并运行直到剩余运行时间或电池电量达到最小允许值,此时它将切换回主电源并为电池充电。

除非电池立即失效,否则您不应有任何停机时间。

这样做:

  • 停止 apcupsd 服务
  • apctest
  • 选择 Perform battery calibration